Manual VIPA System 200V Chapter 5 238-2BC00 - Combination module
HB97E - SM-AIO - Rev. 12/32 5-39
Byte 0 to 11:
The record set 1 contains the 4byte of the record set 0 and additionally
8Byte of module specific diagnostic data.
Record set 1 (Byte 0 to 11):
Byte Bit 7 ... Bit 0 Default
0 ... 3 Content record set 0 (see page before) -
4 Bit 6 ... 0: Channel type
76h: Counter
Bit 7: reserved
76h
5 Number of diagnostic bits per channel 08h
6 Number of similar channels (Counter) 03h
7 Bit 0: Channel error channel 0
Bit 1: Channel error channel 1
Bit 2: Channel error channel 2
Bit 7 ... 3: reserved
00h
8 Error screen channel 0
Bit 0: HW gate open
Bit 1: HW gate closed
Bit 2: Overflow
Bit 3: Comparison value reached
Bit 4: Pulse lost
Bit 7 ... 5: reserved
00h
9 Error screen channel 1
Bit 0: HW gate open
Bit 1: HW gate closed
Bit 2: Overflow
Bit 3: Comparison value reached
Bit 4: Pulse lost
Bit 7 ... 5: reserved
00h
10 Error screen channel 2
Bit 0: HW gate open
Bit 1: HW gate closed
Bit 2: Overflow
Bit 3: Comparison value reached
Bit 4: Pulse lost
Bit 7 ... 5: reserved
00h
11 reserved 00h