Operating instructions, Quick installation
VIEWPAN module
!
The output of the external dc supply must be rated 24 V , ±15%
including fluctuations, min. 40 W. The supply must provide Double Insulation
between Mains parts and 24 V SELV or SELV-E circuit; and a limited-energy
circuit (max. available current 8 A). For the US market this energy limit
can be achieved with an ANSI/UL 248-14 fuse rated 5 A.
For other markets an IEC 60127 T type fuse rated 4 A may also be used.
The power supply unit, designed to supply the complete instrument, is incorporated
in the VIEWPAN module.
24 V In
Terminals 1, 2, and 3.
Connect power to terminal 1 (positive) and
terminal 2 (0 V). To achieve functional
grounding, terminal 3 should be connected
to ground.
24 V Out
Terminals 4 (positive) and 5 can be used
to supply max. 100 mA to logics, like
outputs and inputs.
+24 V In
0 V
Ground
+24 V Out
0 V
1
VIEWPAN
2
0 V
3
Shield
4
5
0 V
6
Shield
+24 VDC In
+24 VDC Out
16