EasyManua.ls Logo

VOLTCRAFT SEM5000 - Overload Alarm Setup

VOLTCRAFT SEM5000
156 pages
Go to English
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
79
9.8 Overload alarm
If a set limit value is exceeded, the energy logger sounds an
alarm, LED ring ashes red and OVERLOAD ashes on the dis-
play. Press any button to stop the alarm. OVERLOAD and red
light will continue to ash.
This function not only protects the energy logger or a connected
load but also signals when the load has exceeded the set limit
during operation. You do not have to constantly monitor the dis-
play.
A power value (W) and a current value (A) can serve as a limit. To
disable the function, set “0” for either of the limits.
With both limits set (e.g. 1000 W and 2 A), the energy logger trig-
gers an alarm when the lower of the two limits is exceeded (in the
example above, the alarm is triggered at 2 A, which corresponds
to a power of 460 W at a mains voltage of 230 V/AC).
In the event of an overload, you can switch off the load and dis-
connect it from the energy logger.
Proceed to the next step if you have already set the CO
2
value before setting the overload alarm. Or access the setup
mode. Pressing the button ve times takes you to the
overload alarm setup menu (see next step).
You can set the overload limit when the display shows
“OVERLOAD”.
Briey pressing the button causes the rst position of the
limit value to ash.
Use the button or to modify the numerical value of
the ashing input position.

Table of Contents

Related product manuals