5
DETAILED PARAMETER DESCRIPTION
P0244 - Analog input AI3 offset (bipolar EBB board)
Adjustable range: -100.0 to 100.0 % Factory setting: 0.0 %
Acesso: Menu Configurations I/O Analog inputs
Description:
Refer to P0234.
P0245 - Analog input AI4 gain (bipolar EBA board)
Adjustable range: 0.000 to 9.999 Factory setting: 1.000
Acesso: Menu Configurations I/O Analog inputs
Description:
Refer to P0234.
NOTE!
Analog Input located on the EBA Optional Board. Refer to the Chapter 7 OPTIONAL ACCESSORIES
AND BOARDS on page 7-1 of the User’s Manual.
P0246 - AI4 Signal Type
Adjustable range: 0 to 4 Factory setting: 0
Acesso: Menu Configurations I/O Analog inputs
Description:
Set the S2.1 switch on the EBB optional board to “ON” position when a current signal is used at the analog
input AI4.
Inverse reference is obtained with the options 2 and 3, i.e., the maximum speed is obtained with the minimum
reference.
Table 5.42: AI4 Signal Type
P0246 Function
0
(0 to 10) V/(0 to 20) mA
1
(4 to 20) mA
2
(10 to 0) V/(20 to 0) mA
3
(20 to 4) mA
4
(-10 to +10) V
NOTE!
This parameter can be changed only with the motor stopped.
P0247 - Analog input AI4 offset (bipolar EBA board)
Adjustable range: -100.0 to 100.0 % Factory setting: 0.0 %
Acesso: Menu Configurations I/O Analog inputs
Description:
Refer to P0234.
MVW3000 | 5-49