5
DETAILED PARAMETER DESCRIPTION
Description:
Used in the digital and relay output functions: N = 0 and in the “Stop Logic” (Disable by N = 0; refer to P0211
and P0212).
P0292 - N=N* Band
Adjustable range: 1 to 100 % Factory setting: 1 %
Acesso: Menu Configurations Control
Description:
Used in the digital and relay output functions: N = N*.
P0295 - Inverter rated current
Adjustable range: 0 to 28 Factory setting: 10
Acesso: Menu Configurations Nominal data Inverter
Description:
It defines the inverter rated current according to the available models.
Table 5.46: Inverter rated current
P0295
Function
0
24 A
1
40 A
2
50 A
3
60 A
4
70 A
5
80 A
6
90 A
7
100 A
8
110 A
9
125 A
10
140 A
11
160 A
12
180 A
13
200 A
14
225 A
15
265 A
16
310 A
17
340 A
18
400 A
19
450 A
20
500 A
21
550 A
22
600 A
23
650 A
24
700 A
25
750 A
26
800 A
27
850 A
28
900 A
NOTE!
This parameter can be changed only with the motor stopped.