5
DETAILED PARAMETER DESCRIPTION
Table 5.68: Function of the analog outputs of the MVC3 board
P0652, P0654,
P0656 and
P0658
Function Full scale
0
Phase Current V
5 V = P0295
1
Phase Current W
5 V = P0295
2
Phase Current U
5 V = P0295
3
Output Frequency
10 V = 120 Hz
4
Angle of the Fundamental Output Voltage
10 V = +180º
5
Modulation Index 5 V = 255
17
Reference of Voltage and Field Current for
Synchronous Machine
10 V = P0462 (A)
10 V = P0463 (V)
18
Position Adjustment of the Absolute
Encoder
10 V = +180°
34
Value fixe at 0 V
-
35
Value fixe at 10 V
-
36
Value fixe at -10 V
-
37
Voltage between Phase A and B
Measured on the Line ISOX Board
5 V = VAB
Rated
38
Voltage between Phase B and C
Measured on the Line ISOX Board
5 V = VBC
Rated
66
Inverter Status
-
86
Indication of A0073
0 V = without A0073
10 V = with A0073
187
Value of Analog Input AI1 MVC3
-
188
Torque Reference of the Inverter
-10 = -200 % *
10 V = +200 % *
* Torque percentage regarding the motor torque.
✓
NOTE!
For other options not described in Table 5.68 on page 5-94,contact WEG Technical Assistance.
P0659 - Analog output gain AO4 MVC3
Adjustable range: 0.000 to 9.999 Factory setting: 1.000
Acesso: Menu → Configurations → I/O → Analog outputs
Description:
It sets the gain of analog output.
P0663 - Analog output offset AO1 MVC3
P0664 - Analog output offset AO2 MVC3
P0665 - Analog output offset AO3 MVC3
P0666 - Analog output offset AO4 MVC3
Adjustable range: -32768 to 32767 Factory setting: -90
Acesso: Menu → Configurations → I/O → Analog outputs
Description:
It sets the offset of analog output.
-32768 = -100 %
32768 = 100 %
MVW3000 | 5-94