QUICK REFERENCE OF PARAMETERS AND FAULTS
Param. Description Adjustable range Factory
setting
Page
P1735
(7)
Bypass of the cell W12 0 = Disable
1 = Mechanical bypass cell
2 = Manual activation of the bypass relay
3 = Automatic bypass after a manageable fault
4 = Automatic bypass by parallel association
0 5-111
P1739
(1)
RL8 Function MVC3 0 = Not used
1 = Output contactor drive for operation with filter type
2
2 = Output contactor drive for operation with permanent
magnet machine
0 5-111
P1892
(7)
Cells in parallel 0 = No parallelism
1 = 2 cells in parallel
2 = 3 cells in parallel
0 5-112
P1893
(7)
Transformer at the input 0 = 1 transformer
1 = 2 transformers
2 = 3 transformers
2 5-112
✓
NOTE!
Quick parameter reference notes:
(1) Parameter can be changed only with the inverter disabled (motor stopped).
(2) Values may change as a function of the ”Motor Parameters”.
(3) Values may change as a function of the parameter P0412 (Lr/Rr Constant).
(4) Values may change as a function of the parameter P0296 (Inverter rated voltage).
(5) Values may change as a function of the parameter P0295 (Inverter rated current).
(6) Values may change as a function of the parameter P0320 (Flying Start/Ride-Through).
(7) Parameter can only be changed with input cubicle opened.
MVW3000 | 1-31