English-5
ENGLISH
Installation and Operation Manual - SSW-05 Plus
4. TECHNICAL DATA:
Example: The code SSW050010T2246PPZ means a 10A SSW-05 Plus, three-phase power
supply in the range from 220 to 460V, manual in Portuguese, PLUS version.
Model
AC Input Power
Control Voltage (A1 and A2)
Power supply
(R/1L1, S/3L2, T/5L3)
Settings
Pedestal Voltage
Acceleration Time
Deceleration Time
Motor Current
Diagnostics
Start Duty
Maximum Number of Starts
per hour
Starting Cycle
Digital Inputs
(90...250Vac 6mA)
Relay
Outputs (1A 250Vac)
Communication
Temperature
Ambient Humidity
Altitude
Degree of Protection
Polution Degree (UL508)
Mounting
Fastening
Enclosure
Electromagnetic Compatibility
(EMC)
Low Voltage
SSW-05 Plus
90 to 250Vac 50/60 Hz (+/- 6Hz)
200 mA
220 to 460 Vac (+10%,-15%) 50/60 Hz (+/- 5Hz) 3
460 to 575 Vac (+10%,-15%) 50/60 Hz (+/- 5Hz) 3
30 to 80% U
N
1 to 20 s
Off to 20 s
30 to 100% I
N
4 ( 1 start every 15 minutes)
3 x I
N
during 10 seconds
0 to 55°C (32to131°F)
5 to 90% Non Condensing
0 to 1000m (up to 13,200 ft (4000m) with
10% output current derating/1000m)
IP 00 (Chassis)
2
DIN 35mm rail or M4 fastening bolts
Molded plastic box
Class A (industrial use)
IEC 60947-4-2 Standard
UL 508 / IEC 60947-4-2
Standards
Motor Overload Protection
Incorrect Phase Sequence
Phase Loss
Immediate Overcurrent
Locked Rotor
Thyristor Overload
Immediate Overload at
By-pass Relay
Overcurrent before By-pass
Frequency out of Tolerance
Internal By-pass Relay
Contact is open
Undervoltage at control voltage
Immediate Undercurrent
(1)
DI1 – Enable/Disable Function
DI2 – Reset Function
Operation Function (13 – 14/23)
Full Voltage Function (14/23 – 24)
Serial Interface (RS232C)
(1)
Enable and Programmed only through serial communication or HMI-SSW05-RS.