EasyManua.ls Logo

Weishaupt WM-L20/2-A R - Check Start Behaviour; Define Partial Load; Set Burner to Automatic Operation; Carry Out Data Backup

Weishaupt WM-L20/2-A R
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
7 Commissioning
83252902 1/2019-09 La
40-84
12. Check start behaviour
Restart burner in Manual operation.
Check start behaviour and if necessary correct ignition position.
If the ignition position has been altered:
Re-check start behaviour.
If the oil temperature has been altered:
Re-check start behaviour.
Restart each point and check combustion values.
13. Define partial load
Select LoadLimits.
Select MinLoad.
Define and set partial load whilst:
Maintain return pressure of 8 bar.
observing data provided by boiler manufacturer,
observing the burner capacity graph [ch.3.4.6].
14. Set burner to automatic operation
Exit level using the [esc] key.
Select Autom/Manual/Off.
Set Automatic.
Exit level using the [esc] key.
If necessary adjust load controller.
15. Carry out data backup
Exit level using the [esc] key.
Select Updating.
Select Param backup.
Select LMV → AZL .
Start data backup by pressing [ENTER] key.
The values have been backed up from the combustion manager to the ABE.
Exit level using the [esc] key.

Table of Contents

Related product manuals