Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
7 Commissioning
83252902 1/2019-09 La
44-84
7.6 Ratings apportionment
The load points are automatically assigned relative to the capacity. Incorrect load
distribution can cause operating problems during the load control.
Assign capacity in % for load point using the following formula.
Enter the calculated capacity for load point in Load.
Load [%] =
Throughput load point
Throughput full load
100