3-4
Initial Checkout
WARNING: TWO DIFFERENT SOURCES OF POWER MAY BE CONNECTED TO THE
SAFEPATH
®
PANEL. DISCONNECT BOTH SOURCES OF POWER BEFORE
SERVICING. FAILURE TO DO SO COULD RESULT IN PROPERTY DAMAGE,
SERIOUS INJURY, OR DEATH TO YOU AND/OR OTHERS.
CAUTION: Connect the AC power source before connecting the battery backup power. Disconnect
the battery backup power before disconnecting the AC power source.
1. Conduct the Initial Checkout procedures as described in Section 3-6 System Checkout.
Final Checkout
2. Remove all EOLRs on Audio and Visual NAC Circuits.
3. Connect all Strobe and Speaker NAC Circuits to the proper connections on the SAFEPATH
®
Motherboard (SCMB). See Figure 3-2 on Page 3-3.
4. Connect all Optional Equipment to the SAFEPATH
®
Panel in accordance with each Installation
Sheet.
5. If the Strobe NAC Circuit is not being used connect a Wheelock, Inc. LISTED 10K Ohm, 1W EOLR to
the terminals on the Mother Board.
6. If Ground Fault Detection is required, connect and align according to Section 3-7 Ground Fault
Detection Sensitivity Adjustment.
7. Perform Final Checkout Procedures as described in Section 3-6 System Checkout.
8. Calculate and Install properly sized backup batteries. (Section 3-8)
Section 3-4 – Prepare a System Wiring Diagram
Wiring Guidelines
Although the SAFEPATH
Panel products incorporate signal verification and noise filtering circuitry on
their inputs, induced voltages or noise on the input wiring can cause improper operation. Therefore, use
shielded twisted pair wire for all dry contact input wiring.
The shield of each cable should be connected only at one end. Each shield of each cable that
connects to the SAFEPATH
Panel is to be connected to the grounding points provided near the
knockout locations on the chassis (see Figure 3-17 on Page 3-15).
The National Electrical Code (NFPA-70) defines two types of circuits for protective signaling systems:
power limited circuits and non-power limited circuits. The SAFEPATH
®
Panel circuits are non-power
limited.
WARNING: ALL SAFEPATH
®
PANEL DRY CONTACT INPUT WIRING AND AUDIO WIRING
SHOULD BE ROUTED AWAY FROM ANY HIGH VOLYAGE OR HIGH CURRENT
WIRING (SUCH AS AC OR DC POWER WIRING, AUDIO POWER WIRING, AND
MOTOR OR RELAY ACTUATION WIRING). DRY CONTACT INPUT WIRING SHALL
BE INSTALLED IN SEPARATE CONDUIT. FAILURE TO DO SO MAY CAUSE
ELECTRICAL SHOCK RESULTING IN PROPERTY DAMAGE AND SERIOUS
INJURY OR DEATH TO YOU AND/OR OTHERS.