Dynamics 2
1 Idle Prop. Gain2 1.0 (0.001, 50.0) _________
2 Rated Prop. Gain2 1.0 (0.001, 50.0) _________
3 Integrator Rate2 2.0 (0.1, 50.0) _________
4 Derivative Ratio2 5.0 (1.0, 100.0) _________
5 Window Width2 10.0 (1.0, 50.0) _________
6 Gain Ratio2 1.0 (0.1, 10.0) _________
======================================================================
S.S4
Speed Setting
1 Start Speed 300.0 (200.0, 1000.0) _________
2 Idle Speed 350.0 (200.0, 1000.0) _________
3 Rated Speed 520.0 (300.0, 1000.0) _________
4 Raise Limit 572.0 (300.0, 1000.0) _________
5 Raise/Lower Rate 1.0 (0.1, 100.0) _________
6 Load Transfer Rate 1.0 (0.1, 100.0) _________
7 Spd Set at 4mA 350.0 (200.0, 1000.0) _________
8 Spd Set at BP,mA 8.0 (4.0, 20.0) _________
9 Spd Set at BP,RPM 350.0 (200.0, 1000.0) _________
10 Spd Set at 20mA 540.0 (200.0, 1000.0) _________
11 Tach at 4mA Output 0.0 (0.0, 1000.0) _________
12 Tach at 20mA Output 600.0 (0.0, 1000.0) _________
13 Spd Set at 4mA Output 0.0 (0.0, 1000.0) _________
14 Spd Set at 20mA Output 600.0 (0.0, 1000.0) _________
======================================================================
S.S5
Kw Setting
1 Rated KW 1280.0 (100.0, 10000.0) _________
2 20mA KW Load Input 1500.0 (100.0, 10000.0) _________
3 Kw Droop Set(%) 5.0 (0.0, 10.0) _________