EasyManua.ls Logo

Worcester Greenstar 8000 Life GR8300iW 30 R

Worcester Greenstar 8000 Life GR8300iW 30 R
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Settings in the service menu
Greenstar 8000 Life – 6720883866 (2019/04)
46
Menu 2 (L.2) Hydraulic settings
Press the ( key and * key at the same time, until L.A is displayed.
Keep pressing the arrow key , until L.2 is displayed.
To confirm the selection: Press the OK key.
Select and set the service function.
The basic settings are depicted as highlighted in the following table.
Table 18 Menu 2: Hydraulic settings
Menu 3 (L.3) Basic Settings
Press the ( key and * key at the same time, until L.A is displayed.
Keep pressing the arrow key , until L.3 is displayed.
To confirm the selection: Press the OK key.
Select and set the service function.
The basic functions are depicted as highlighted in the following table.
Service function L.2 Settings/adjustment range Remark/restriction
2-A1 Low-loss header 0: No low-loss header present
1: Temperature sensor connected at the
appliance
2: Low-loss header connected to the module
3: Low-loss header without temperature sensor
This setting defines, where the temperature
sensor for the low-loss header is connected.
2-A2 Hot water system 0: Not installed
1: 3-way valve installed
2: Cylinder primary pump installed
2-A3 Hydraulic configuration for heating
circuit 1
0: No independent heating pump installed
•1:
2: Heating pump after low-loss header
3: Heating pump connected to the module
This service function will only be available, if
service function 2-A1 is set.
2-A4 Hydraulic configuration heating pump 0: No pump
1: Heating pump
Service function L.3 Settings/adjustment range Remark/restriction
3-b1 Maximum heat output 50 … 100 % Set thermal output in percent.
Measure gas flow rate.
Compare measured result with the setting
tables ( page 69). Correct the setting in
the case of any deviation.
3-b2 Standby time 3 ... 5 ... 60 minutes The time interval determines the minimum dela
between starting and restarting the boiler.
If an outside temperature-controlled heating
controller is connected, this setting is optimised
by the heating controller.
3-b3 Temperature interval for switching off
the burner and switching it on again
-15 ... -6 ... -2 K ( °C) Difference between current flow temperature
and set flow temperature up to the point when
the burner is switched on.
If an outside temperature-controlled heating
controller is connected, this setting is optimised
by the heating controller.
3-C1 Maximum power on DHW 50 … 100 %
3-C2 DHW circulation pump ON
OFF
3-C3 DHW circulation pump, number of
starts
1: 1 x 3 min/h
2: 2 x 3 min/h
3: 3 x 3 min/h
4: 4 x 3 min/h
5: 5 x 3 min/h
6: 6 x 3 min/h
7: permanent
3-C7 Thermal disinfection OFF
•ON
This service function activates heating up the
storage to 75 °C.
Undertaking Thermal Disinfection
( chapter 7.3).
Thermal Disinfection will be completed after 30
minutes of heating the storage up to 75 °C.

Table of Contents

Related product manuals