Fault finding and diagnosis
Greenstar Heatslave II
ErP -
6 720 813 344 (2014/09)48
Fig. 87
8.4 Factory reset and fault codes
8.4.1 Factory reset
To reset changes made in Menu 2 back to the factory default setting:
Fig. 88
1. Press and hold the and buttons for at least
5 seconds. The screen will then display code BE with the spanner
symbol.
2. Press the button and “reset” will be displayed with the tick
symbol for 3 seconds. After 3 seconds the display will revert to the
normal operation screen.
Fig. 89
8.4.2 Locking or Blocking fault conditions
Should a fault develop with this boiler (or the system), the boiler will
enter into a Locking or Blocking condition.
Locking condition
• The boiler display will flash a warning triangle.
• A 3 digit cause code will flash on the display during a Locking error.
• An alpha numeric fault code will be displayed indicating the fault
group.
• The operation and fault indicator will flash on the front of the
appliance.
Manual intervention is required following clearance of the fault.
▶ Press the reset button on the boiler fascia.
Blocking condition
• The boiler will stop operating and no fault code will be displayed.
• An alpha numeric fault code is accessed in the info menu by pressing
the spanner/return button.
• A 3 digit cause code is also accessed in the info menu by pressing the
spanner/return button.
• The condition will clear automatically when the associated fault
clears e.g. waiting for an area of the boiler to cool down.
• In some cases a Blocking error has a defined time duration prior to
changing to a Locking condition.
2.7A Demand/fault
LED (blue light) activation
O = The blue light will only
operate as a flashing fault
alert.
1 = The blue light will operate
as a boiler operation and
fault alert.
This is set to 1 by default.
Menus 3 and Test are empty and are not used on this
appliance.
Any changes made to Menu 1 are not reset by these
actions.