EasyManua.ls Logo

Xantrex XDC 10-1200 - AC Input Wire; Table 2-2 AC Wire Specification for 6000 Watt Units; Table 2-3 AC Wire Specification for 12000 Watt Units

Xantrex XDC 10-1200
284 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
2–8 TM-XDOP-01XN
AC Input Wire
The manufacturer recommends the AC input wire specified in Table 2-2 and Table
2-3. This must be permanently connected to an approved AC distribution box with
suitably rated over-current protection. If you require a special cord, contact the
manufacturer.
f
Table 2-2
AC Wire Specification for 6000 Watt Units
AC Input Voltage Range Wire
190–242Vac, 47–63Hz,
3-phase, 4 wire (standard)
4 x 10 AWG (3 wire plus safety ground), stranded
copper, 60
°C minimum, 300V, 0.800 in.
maximum cable diameter, rated for 25A.
342–500Vac, 47–63Hz,
3-phase, 4 wire (HV-Input)
4 x 14 AWG (3 wire plus safety ground), stranded
copper, 60
°C minimum, 600V, 0.800 in.
maximum cable diameter, rated for 13A.
Table 2-3
AC Wire Specification for 12000 Watt Units
AC Input Voltage Range Wire
190–242Vac, 47–63Hz,
3-phase, 4 wire (standard)
4 x 6 AWG (3 wire plus safety ground), stranded
copper, 60
°C minimum, 300V, outside diameter
(OD) of cable is 1in., rated for 50 A.
342–500Vac, 47–63Hz,
3-phase, 4 wire (HV-Input)
4 x 10 AWG (3 wire plus safety ground), stranded
copper, 60
°C minimum, 600V, outside diameter
(OD) of cable is 1in., rated for 25 A.
TM-XDOP-01XN.book Page 8 Monday, July 17, 2006 11:19 AM