overvoltage
(220V: U0-05
390 alarm,
380V: U0-05
780V alarm)
2. not connect
regenerative resistor
3. regenerative
damaged or resistor too
large
2. connect regenerative
resistor
3. check if the regenerative
resistor matched power
04
0
E-040
Bus
undervoltage(2
20V: U0-05
140.
380V: U0-05
300)
1. Power grid voltage
too low
2. instant power off
1. check the grid
fluctuation
2. use constant voltage
source
1
E-041
Drive power
off
Drive power cut off
Check the power supply
3
E-043
Bus voltage
charging failure
Hardware damage
Please note if there is relay
ON/OFF sound when
drive power on
06
0
E-060
Module
temperature too
high
1. long time running
with large load
2. environment
temperature too high
3. fan has error
1. consider change the
motor capacity(mointor
U0-02, motor present
torque) decrease the load
2. good ventilation,
decrease environment
temperature
3. check if the fan works
when servo enabled,
module temperature
U0-06≥45, fan will
work.
1
E-061
Motor
1. long time running
1. decrease the load