8 expansion devices
Analogue Input (AD)
Items
Voltage Input Current Input
Analogue Input Range
DC05V010V
DC020mA420mA
Max Input Range
DC±18V DC040mA
Analogue Output -
Digital Input Range -
Digital Output Range 14 bits binary (016383)
Distinguish Ratio 1/16383(14Bit); the convert data is stored in PLC in form of Hex. (14Bit)
PID Output Value 0K4095
Integral precision 0.8%
Convert Speed 20ms/CH
Power Supply DC24V±10%100mA
0V
24V
C1
C0
AI0 VI1 C2 AI2 VI3
AI3C3VI2A11VI0
CH NAME
SIGNAL CH NAME
SIGNAL
AI0 Current analogue input AI1 C
urrent analogue input
VI0 Voltage analogue input
VI1 Voltage analogue input
CH0
C0 COM of CH0
CH1
C1 COM of CH1
AI2 Current analogue input AI3 Current analogue input
VI2 Voltage analogue input
VI3 Voltage analogue input
CH2
C2 COM of CH2
CH3
C3 COM of CH3
24V +24V power supply
-
0V COM of power supply
8-3-4XC-E4DA
Specification 2
Terminal Arrangement
3
Brief Introduction 1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xinje XC3 Series and is the answer not in the manual?

Xinje XC3 Series Specifications

General IconGeneral
SeriesXC3
TypePLC
Communication PortsRS232, RS485
Power Supply24V DC
CPU Type32-bit
Programming SoftwareXCP Pro
Operating Temperature55°C
Analog InputsOptional, depends on expansion modules
Analog OutputsOptional, depends on expansion modules