Product Guide
VESDA ECO Detector by Xtralis
20 Installation
The relay contact
s are rated to a maximum voltage of 30Vdc and a maximum
current of 1A dc. Should higher power control be required, the
ECO
used to control external slave relays.
If
a voltage greater than that supplied to the ECO is required to be used on the
contacts of the slave relay, it is solely the responsibility of the Installer and Designer
of the application to ensure that the rating, insulation and safety requirements of
co
mponents using that higher voltage are met and complied with and that they are
sufficiently isolated from the ECO product.
Figure 10 R
elay Connection to Fans and Beacons
Xtralis assumes no liability for any damage or injury
result of using the ECO product to control voltages above those f
which it is rated.
VESDA ECO Detector by Xtralis
17898_05
s are rated to a maximum voltage of 30Vdc and a maximum
ECO
relays can be
a voltage greater than that supplied to the ECO is required to be used on the
contacts of the slave relay, it is solely the responsibility of the Installer and Designer
of the application to ensure that the rating, insulation and safety requirements of
mponents using that higher voltage are met and complied with and that they are
elay Connection to Fans and Beacons
Xtralis assumes no liability for any damage or injury
caused as a
result of using the ECO product to control voltages above those f