Product Guide VESDA ECO Detector by Xtralis
62 Troubleshooting 17898_05
If/when the Yellow fault indicator is illuminated continuously then there is a Major Fault present within the unit.
A Major Fault is a state in which the ability of the product to communicate a gas level or alarm condition may be
impaired.
When the Yellow fault indicator is flashing, a Minor Fault is present within the unit.
A Minor Fault is a state where operation of the unit may be impaired, but this does not affect the ability of the unit to
correctly measure gas levels or communicate alarm conditions.
In either case, it is important not to leave the unit in either condition and to use Xtralis VSC to determine the nature of the fault
and the corrective action required.
Below is a list of the fault and warning conditions that may occur, and will be indicated by Xtralis VSC with the description of
each and the corrective action
VSC
Fault
Number
Root cause
In Field
Serviceable
(Y/N)
Fault Solution (Visible within VSC via F1)
2030
There has been a power
Failure Since this error was
last Reset
N
The detector has been powered down since the last inspection.
Click reset to clear error.
If unable to clear error replace detector main PCB and reconfigure
2031
There has been a system
Reboot since this error has
been last reset
N
The detector has rebooted since the last inspection.
Click reset to clear error.
If unable to clear error replace detector main PCB and reconfigure