Product Guide VESDA ECO Detector by Xtralis
66 Troubleshooting 17898_05
VSC
Fault
Number
Root cause
In Field
Serviceable
(Y/N)
Fault Solution (Visible within VSC via F1)
2001
System RAM failure.
An internal Memory error
has occurred in the IO
Board
N
The detector suffered an internal memory failure try to reboot / re-commission
detector. If unable to reboot replace main PCB
2002
System configuration write
failed . An internal
Memory error has occurred
in the IO Board
N
The detector suffered an internal software failure try to reboot / re-commission
detector. If unable to reboot replace main PCB
2003
System configuration read
failed . An internal
Memory error has occurred
in the IO Board
N
The detector suffered an internal software failure try to reboot / re-commission
detector. If unable to reboot replace main PCB
2004
An internal Software fault
has occurred in the IO
Board
N
The detector suffered an internal software failure, try to reboot / re-commission
detector. If unable to reboot replace main PCB
2005
Sensor module ROM CRC
failure. An internal
Memory error has occurred
in the Cartridge
N
The Sensor cartridge suffered an internal memory failure try to reboot. If unable to
clear replace sensor cartridge and re commission