(Y/N)
Fault Solution (Visible within VSC via F1)
2011
SD card failure. The SD
Card is not responding -
possible hardware or card
fault
Y
The detector cannot recognise the SD card. Remove and re insert SD card and
click reset to clear. If unable to clear error replace SD card. If error persists
replace main PCB
2012
The monitored Air Flow is
greater than the Major
Threshold High Limit
Y
Sample air flow increased above acceptable limits. Select “Reset” to clear. If
unable to clear the fault, check the ECO detector inlet and outlets, ASD and
sample pipe-work installation. If the error persists and the ASD is in good
operation, check the sensor cartridge for blockages and clogged filters. Finally, if
the flow reading does not return to normal after all of the above checks, attempt
to re-“Normalise” the airflow. If this does not cure the problem, replace the
sensor cartridge.
2013
The monitored Air Flow is
less than the Major
Threshold Low Limit
Y
Sample air flow decreased below acceptable limits. Select “Reset” to clear. If
unable to clear the fault, check the ECO detector inlet and outlets, ASD and
sample pipe-work installation. If the error persists and the ASD is in good
operation, check the sensor cartridge for blockages and clogged filters. Finally, if
the flow reading does not return to normal after all of the above checks, attempt
to re-“Normalise” the airflow. If this does not cure the problem, replace the
sensor cartridge.
2015
Relay 1 fails to operate as
expected
N
Detector relay 1 failed
Replace main PCB and re-commission