EasyManua.ls Logo

Xtralis VESDA ECO - Page 83

Xtralis VESDA ECO
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VESDA ECO Detector by Xtralis Product Guide
17898_05 Troubleshooting 73
VSC
Fault
Number
Root cause
In Field
Serviceable
(Y/N)
Fault Solution (Visible within VSC via F1)
2154
Zero calibration under
range. Signal too noisy or
more than 10% of range
beyond applied gas level
Y
Sensor cartridge zero calibration under range.
Check calibration gas, connections and settings then recalibrate. If error persists,
replace sensor cartridge and re-commission
2164 Sensor Module Fault
N
Sensor cartridge watchdog initiated a reset. Reset error via VSC. If error persists,
replace sensor cartridge and re-commission. Report failure via Xtralis service
reporting system
2100
Sensor Module Fault
Sensor temperature over
range
N
The sensor cartridge has been exposed to temperatures above its specified
operating temperature. Check sample air temperature. Click clear to reset. If
unable to reset and sample air temperature is within specified limits replace
sensor cartridge and re-commission. If unable to clear error replace complete
detector and re commission.
2101
Sensor Module Fault
Sensor temperature under
range
N
The sensor cartridge has been exposed to temperatures below its specified
operating temperature. Check sample air temperature. Click clear to reset. If
unable to reset and sample air temperature is within specified limits replace
sensor cartridge and re-commission. If unable to clear error replace complete
detector and re commission.
2102
Sensor Module Fault
Sensor ROM Error
N
The Sensor assembly suffered an internal memory failure try to reboot. If unable
to clear replace sensor cartridge and re commission

Table of Contents

Related product manuals