VESDA ECO Detector by Xtralis Product Guide
17898_05 Troubleshooting 75
VSC
Fault
Number
Root cause
In Field
Serviceable
(Y/N)
Fault Solution (Visible within VSC via F1)
2111
Sensor Module Fault
Sensor communication
error
N
The Sensor cartridge suffered an internal communications failure. Replace sensor
cartridge and re commission
2119
Sensor life elapsed.
The sensor needs to be
replaced as its operating
life has expired.
N
The sensor cartridge has reached the end of its serviceable life. Replace sensor
cartridge and re-commission
2120 Sensor Module Fault
N
The Sensor cartridge suffered an internal communications failure. Replace sensor
cartridge and re commission
2121 Sensor Module Fault
N
The Sensor cartridge suffered an internal communications failure. Replace sensor
cartridge and re commission

Table of Contents