9 Troubleshooting
9.1 Common problems
Symptom Remedy
The log in fails. Check that the user name and password are correct.
The default password is ef56 for config and cd34 for
operator.
If the default passwords are changed, then make
sure that the new password is available.
The passwords are case-sensitive.
If the password is lost, then contact the local sales
and service representative.
The computer does not connect to the web tool. For more information, ,see Connect a computer
directly to the web tool (page 20).
For more information, ,see For more
information, ,see Check and change the IP address
(page 35).
If the IP address has been changed, then restart the
base unit by disconnecting and connecting the
power supply.
Graphs do not appear in the web tool. Download the Java runtime environment and install
it.
For more information, ,see For more
information, ,see Configure Java on the computer
(page 19).
The wrong language is appears. Change the language with the operator panel. For
more information, ,see Change the language (page
32).
Change the language with the web tool. For more
information, ,see Change the language (page 25).
There is no communication with the other units.
The Active alarms list and Alarm and event log show
a communication alarm.
The Active alarms list and Alarm and event log shows
the message No pump memory sync.
The operator panel menus are not updated when the
buttons are pressed.
The base unit does not register values from the
power analyzer.
The relay module does not correctly indicate the
alarms
Make sure that the wires are connected correctly. For
more information, ,see Electrical Installation (page
11).
If the communication with the higher-level system
does not work on Ext 1, then try to switch the A and B
wires on the terminals 41 and 42.
There are problems with the sensors.
The Active alarms list and Alarm and event log show
a short circuit although the sensor is connected.
A sensor shows incorrect values.
If the wires for the sensor are long, then compensate
the distance. For more information, ,see Correct the
measurement error due to long leads (page 28).
Check that the wires are connected correctly.
Check that the sensor functions.
If the sensor gets its power supply from the base
unit, then measure the power supply.
Replace the sensor.
9 Troubleshooting
52 MAS 711 Installation, Operation, and Maintenance Manual