EasyManua.ls Logo

Xylem hydrovar hv 1.1 - Mode, Control Response, and Units; Inverter Settings; Maximum and Minimum Frequency

Xylem hydrovar hv 1.1
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42
13.3 Mode
Mode
Controller
Select with buttons Ð and Ï between:
Multicontroller sequence control for max. 4 pumps
Controller pressure control for a single pump If only one HYDROVAR-pump is in
operation, set Controller.
If more than one HYDROVAR-pumps are working together via the RS485-interface, the
Multicontroller must be selected.
Actuator external frequency setting. The application Actuator is only used, if you
have an external controller and the HYDROVAR works like a standard frequency
converter (external frequency signal 0,5-4,5VDC to the terminals X2/1 and X2/2).
Press
Î
on the controller to change to
13.4 Control Response
Regulation Mode
Normal
Normal: Speed is increased with falling actual value
Signals. (e.g.: Control at constant output pressure).
Inverse: Speed is reduced with falling actual value
signal, (e.g.: Control of constant suction pressure or at
constant level before the pump).
Press
Î
on the controller to change to
13.4.1 Dimension unit
Dimension unit
Bar
Here you could choose your favourite unit (with
buttons Ð and Ï) Bar, psi or % for the 1
st
display.
Press
Î
on the controller to change to
13.5 Submenu Inverter
Submenu
Inverter
To enter this menu you have to press the Ð
key, to
leave the menu, press the Î key longer than 3 sec.
Press
Î
on the controller to change to
13.5.1 Maximum Frequency
Max. Frequency
50.0 Hz
Possible setting between min. 40 and max. 70 Hz.
Attention: Settings higher than 50 Hz may overload the
motor!
Settings of 10% above nominal frequency cause 33%
more power consumption!

Table of Contents

Related product manuals