5-52
U1-18
Motor second-
ary current (Iq)
Monitors the calculated value of the
motor secondary current.
Motor rated
secondary current
0.1% A A 51H
Mot SEC Cur-
rent
U1-19
Motor exciting
current (Id)
Monitors the calculated value of the
motor excitation current.
Motor rated
secondary current
0.1% A A 52H
Mot EXC Cur-
rent
U1-20
Output fre-
quency after
soft-start
Monitors the output frequency after a
soft start.The frequency given does not
include compensations, such as slip
compensation.
Max. frequency
0.01
%
A A 53H
SFS Output
U1-21
ASR input
Monitors the input to the speed control
loop.
Max. frequency
0.01
%
No A 54H
ASR Input
U1-22
ASR output
Monitors the output from the speed con-
trol loop.
Motor rated
secondary current
0.01
%
No A 55H
ASR Output
U1-23
ASR integral
value
Monitors the integral value from the
speed control loop.
Motor rated
secondary current
0.01
%
No A 56H
ASR Integral
U1-25
Terminal AI4
input voltage
Monitors the input voltage of the multi-
function analog input 4.
10 V 0.1% A A 58H
AI4 Input
U1-26
Output voltage
reference (Vq)
Monitors the Inverter internal voltage
reference for motor secondary current
control.
Voltage class
AC3300 V(AC6600
V)
1 V A A 59H
Voltage Ref
(Vq)
U1-27
Output voltage
reference (Vd)
Monitors the Inverter internal voltage
reference for motor excitation current
control.
Voltage class
AC3300 V(AC6600
V)
1 V A A 5AH
Voltage Ref
(Vd)
U1-28
Software
No.(FPGA)
(Manufacturer’s FPGA software No.) [No.] A A 5BH
FPGA Rev.
U1-32
ACR output of
q axis
Monitors the current control output
value for the motor secondary current.
Voltage class 0.1% A A 5FH
ACR(q) Output
U1-33
ACR output of
d axis
Monitors the current control output
value for the motor excitation current.
Voltage class 0.1% A A 60H
ACR(d) Output
U1-34
OPE fault con-
stant Shows the first constant number where
an OPE fault was detected.
Con-
stant
Num-
ber
A A 61H
OPE Detected
U1-41
Actual fin
temperature
Monitors the temperature of fin in A1
cell.
(temperature is displayed above about
80°C)
1°CA A 68H
Actual Fin
Temp
Constant
Number
Name
Description 100% Value
Min.
Unit
Control
Methods
MEMOBUS
Register
Display
Open-
loop
Vector
Flux
Vector