EasyManua.ls Logo

YASKAWA iQpump Micro

YASKAWA iQpump Micro
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
YASKAWA TOEP YAIQPM 01A iQpump Micro Quick Start Procedure
iQpump Micro
Quick Start Procedure
Page 12
of 31
Install the 24 V Transducer Power Supply (continued)
5
STEP
5.13
Connect the ground wire to the 24V Power Supply at ground terminal FE.
Route the free end of the ground wire to the front of the 24V Power Supply via the through-slot as shown in Table
1.10 and connect the ground wire. Tighten the screw to 0.5 ~ 0.6 Nm or (4.4 ~ 5.3 in lbs) using an M3 Phillips
screwdriver.
Table 1.10 Connect Ground Wire to 24V Power Supply
IP20/NEMA 1, UL Type 1 and IP66/NEMA 4X, UL Type 4X
Ground Wire
24V Power Supply
Ground Terminal (FE)
J2
FE
Through-slot
for 24V Power
Supply Wiring
5.14
Connect the white J2 lead wire to terminal A2 on drive terminal block TB1-2.
Route the free end of the J2 wire to the A2 terminal on the drive via the through-slot on the 24V Power supply as
shown in Table 1.11.
Table 1.11 Connect J2 Lead Wire to Drive
IP20/NEMA 1, UL Type 1 and IP66/NEMA 4X, UL Type 4X
TB1-2 (A2) Terminal
A2
TB1-2
TB1-1
J
2
J2 Lead Wire
(White)
Ground Wire
J2
FE
Through-slot
for 24V Power
Supply Wiring

Other manuals for YASKAWA iQpump Micro