EasyManua.ls Logo

YASKAWA L1000A - Page 178

YASKAWA L1000A
247 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
B Parameter Table
176 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide
E2: Motor Parameters
No. Name Description Setting
E2-01
<4> Default setting value varies by the drive model (o2-04).
<10> The display resolution depends on the rated output power of the drive. Models CIMR-LU20008 to 20033, 40005 to 40018, and
50003 to 50013 display values in 0.01 A units, while models CIMR-LU20047 to 20415, 40024 to 40605, and 50017 to 50200
display values in 0.1 A units.
Motor Rated Current
Sets the motor nameplate full load current in Amps. Automatically set during
Auto-Tuning.
Default:
<4>
Min: 10% of drive
rated current
Max: 200% of
drive rated
current
<10>
E2-02 Motor Rated Slip Sets the motor rated slip. Automatically set during Auto-Tuning.
Default:
<4>
Min: 0.00 Hz
Max: 20.00 Hz
E2-03 Motor No-Load Current Sets the no-load current for the motor. Automatically set during Auto-Tuning.
Default:
<4>
Min: 0 A
Max: E2-01 <10>
E2-04 Number of Motor Poles Sets the number of motor poles. Automatically set during Auto-Tuning.
Default: 4
Min: 2
Max: 48
E2-05
Motor Line-to-Line
Resistance
Sets the phase-to-phase motor resistance. Automatically set during Auto-Tuning.
Default:
<4>
Min: 0.000 Ω
Max: 65.000 Ω
E2-06 Motor Leakage Inductance
Sets the voltage drop due to motor leakage inductance as a percentage of motor rated
voltage. Automatically set during Auto-Tuning.
Default:
<4>
Min: 0.0%
Max: 40.0%
E2-07
Motor Iron-Core
Saturation Coefficient 1
Sets the motor iron saturation coefficient at 50% of magnetic flux. Automatically set
during Auto-Tuning.
Default: 0.50
Min: 0.00
Max: 0.50
E2-08
Motor Iron-Core
Saturation Coefficient 2
Sets the motor iron saturation coefficient at 75% of magnetic flux. Automatically set
during Auto-Tuning.
Default: 0.75
Min: E2-07
Max: 0.75
E2-09 Motor Mechanical Loss Sets the motor mechanical loss as a percentage of motor rated power (kW).
Default: 0.0%
Min: 0.0%
Max: 10.0%
E2-10
Motor Iron Loss for Torque
Compensation
Sets the motor iron loss.
Default:
<4>
Min: 0 W
Max: 65535 W
E2-11 Motor Rated Power
Sets the motor rated power in kilowatts (1 HP = 0.746 kW). Automatically set during
Auto-Tuning.
Default:
<4>
Min: 0.00 kW
Max: 650.00 kW
TOEP_C710616_38H_7_0.book 176 ージ 015年11月11日 水曜日 午後7時40