E5: PM Motor Settings
<4> Default setting value is dependent on the drive model (o2-04).
<10> The display resolution depends on the rated output power of the drive. Models CIMR-LU20008 to 20033, 40005 to 40018, and
50003 to 50013 display values in 0.01 A units, while models CIMR-LU20047 to 20415, 40024 to 40605, and 50017 to 50200
display values in 0.1 A units.
No. Name Description Setting
E5-02
<1>
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<4> Default setting value is determined by the drive model (o2-04).
<10> The display resolution depends on the rated output power of the drive. Models CIMR-LU20008 to 20033, 40005 to 40018, and
50003 to 50013 display values in 0.01 A units, while models CIMR-LU20047 to 20415, 40024 to 40605, and 50017 to 50200
display values in 0.1 A units.
<43> When PG-E3 option connected: Max setting = 48
Motor Rated Power Sets the rated capacity of the motor.
Default:
<4>
Min: 0.10 kW
Max: 650.00 kW
E5-03
<1>
Motor Rated Current Sets the motor rated current.
Default: <4>
Min: 10% of drive
rated current
Max: 200% of
drive rated
current
<10>
E5-04
<1>
Number of Motor Poles Sets the number of motor poles.
Default: 12
Min: 2
Max: 120
<43>
E5-05
<1>
Motor Stator Resistance
(Single Phase)
Sets the stator resistance (1 phase value).
Default:
<4>
Min: 0.000 Ω
Max: 65.000 Ω
E5-06
<1>
Motor d-Axis Inductance Sets the d-axis inductance.
Default: <4>
Min: 0.00 mH
Max: 600.00 mH
E5-07
<1>
Motor q-Axis Inductance Sets the q-axis inductance.
Default: <4>
Min: 0.00 mH
Max: 600.00 mH
E5-09
<1>
Motor Induction Voltage
Constant 1
Sets the induced phase peak voltage in units of 0.1 mV (rad/s) [electrical angle].
When setting this parameter, E5-24 should be set to 0.0.
Default:
<4>
Min: 0.0 mV/(rad/
s)
Max:
6500.0 mV/(rad/s)
E5-11 Encoder Offset
Sets the offset between the rotor magnetic axis and the encoder zero position. Set
during Encoder Offset Tuning.
Default: 0.0 deg
Min: -180 deg
Max: 180 deg
E5-24
Motor Induction Voltage
Constant 2
Sets the induced phase-to-phase rms voltage in units of 0.1 mV/(r/min) [mechanical
angle].
When setting this parameter, E5-09 should be set to 0.0.
Default:
0.0 mV/(r/min)
Min:
0.0 mV/(r/min)
Max:
6500.0 mV/(r/
min)