3 Electrical Installation
YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide 41
Electrical Installation
3
Note: When connecting peripheral devices and options to the terminals –, +1, +3, B1, and B2, refer to the instruction manuals for each
device. For more information, contact Yaskawa or your nearest sales representative.
Table 12 Wire Gauge and Torque Specifications (Three-Phase 600 V Class)
40260
R/L1, S/L2, T/L3 3/0 × 2P 2/0 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 3/0 × 2P 2/0 to 600
–, +1 3/0 to 600
+3 1 to 325 M10
18 to 23
(159 to 204)
2 2 to 350 M12
32 to 40
(283 to 354)
40304
R/L1, S/L2, T/L3 4/0 × 2P 3/0 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 4/0 × 2P 3/0 to 600
–, +1 4/0 to 600
+3 3/0 to 600 M10
18 to 23
(159 to 204)
1 1 to 350 M12
32 to 40
(283 to 354)
40370
R/L1, S/L2, T/L3 300 × 2P 4/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 300 × 2P 4/0 to 300
–, +1 3/0 to 300
+3 3/0 to 300
1 1 to 3/0
40450
R/L1, S/L2, T/L3 3/0 × 4P 3/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 3/0 × 4P 3/0 to 300
–, +1 1/0 to 300
+3 1/0 to 300
1/0 1/0 to 300
40605
R/L1, S/L2, T/L3 300 × 4P 4/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 300 × 4P 4/0 to 300
–, +1 1/0 to 300
+3 1/0 to 300
2/0 2/0 to 300
<1> When using the wire of this gauge in accordance with IEC/EN 61800-5-1, install an ELCB.
<2> When using the wire of this gauge in accordance with IEC/EN 61800-5-1, install an ELCB, or use copper wire of 10 mm
2
(AWG 8).
Model
CIMR-LU
Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
Nm (lb.in.)
50003
50004
R/L1, S/L2, T/L3 14 14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 14 14 to 10
–, +1, +2 14 to 10
B1, B2 14 to 10
10 14 to 10
50006
R/L1, S/L2, T/L3 14 14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 14 14 to 10
–, +1, +2 14 to 10
B1, B2 14 to 10
10 12 to 10
Model
CIMR-LU
Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
Nm (lb.in.)