T1-04: Motor Rated Current
Sets the motor rated current according to the motor nameplate value. Set the motor rated current between 50% and 100%
of the drive rated current for optimal performance in OLV or CLV. Enter the current at the motor base speed.
T1-05: Motor Base Frequency
Sets the motor rated frequency according to the motor nameplate value. If a motor with an extended speed range is used
or if the motor is used in the field weakening area, enter the maximum frequency to E1-04 (E3-04 for motor 2) after
Auto-Tuning is complete.
T1-06: Number of Motor Poles
Sets the number of motor poles according to the motor nameplate value.
T1-07: Motor Base Speed
Sets the motor rated speed according to the motor nameplate value. If a motor with an extended speed range is used or if
the motor is used in the field weakening area, enter the speed at base frequency to T1-07.
T1-08: PG Number of Pulses Per Revolution
Sets the number of pulses from the PG encoder. Set the actual number of pulses for one full motor rotation.
Note: T1-08 will only be displayed in CLV.
T1-09: Motor No-Load Current
Sets the no-load current for the motor. The default setting displayed is no-load current automatically calculated from the
output power set in T1-02 and the motor rated current set to T1-04. Enter the data listed on the motor test report. Leave
this data at the default setting if the motor test report is not available.
No. Parameter Name Setting Range Default
T1-04 Motor Rated Current
10 to 200% of drive rated
current
Depending on o2-04
No. Parameter Name Setting Range Default
T1-05 Motor Base Frequency 0.0 to 200.0 Hz 60.0 Hz
No. Parameter Name Setting Range Default
T1-06 Number of Motor Poles 2 to 48 4
No. Parameter Name Setting Range Default
T1-07 Motor Base Speed 0 to 24000 r/min 1750 r/min
No. Parameter Name Setting Range Default
T1-08 PG Number of Pulses Per Revolution 0 to 60000 ppr 1024 ppr
No.
<1> The value will have two decimal places (0.01 A) in the drive models 20008 to 20033,40005 to 40018 and 50003 to 50013 (refer to
Table 55, Table 56 and Table 57), and one decimal place (0.1 A) in the drive models 20047 to 20415, 40024 to 40605 and 50017 to
50200.
Parameter Name Setting Range Default
T1-09 <1> Motor No-Load Current
0 to [T1-04] A
(Max: 0 to 2999.9)
–