4.4 MP2000 Series Machine Controller Parameter Details
4.4.2 Motion Setting Parameter Details
4-53
A typical example of a zero point return operation is shown below.
Refer to 6.2.3 Zero Point Return (ZRET) for details.
( 26 ) Step Travel Distance
OL40
Creep Rate
Setting Range Setting Unit Default Value
−2
31
to 2
31
−1
Depends on
Speed Units.
500
Description
Set the creep speed for a zero point return operation after the ZERO signal is detected.
The setting unit for this parameter depends on the Speed Unit Selection (OW03, bits 0 to 3), but
the result of applying the speed unit setting is not shown here.
OL42
Zero Point Return Travel Distance
Setting Range Setting Unit Default Value
−2
31
to 2
31
−1
Reference unit 0
Description
Set the distance from where the signal is detected to the zero point position.
(cont’d)
Speed
Start
㧔OL40㧕
㧔OL42㧕
DEC signal
Phase-C pulse
Creep Rate
Zero Point Return
Travel Distance
Width of
Starting
Point
Position
Output
㧔OL3E㧕
Approach Speed
㧔OL10㧕
Speed Reference
Setting
Position
OL44
Step Travel Distance
Setting Range Setting Unit Default Value
0 to 2
31
−1
Reference unit 1000
Description
Set the moving amount for STEP commands.
Refer to 6.2.7 Relative Position Mode (STEP) (Step Mode) for details on STEP commands.
(%)