Installation and Operation Guide SOLECTRIA XGI 1500 (Rev A, April 2019)
21 of 77
AC Connections
3.6
The AC connections consist of the 3 AC Phases (L1, L2, and L3), Neutral and Ground. AC wires must be rated
for at least 600 VAC. Use wires within the ranges shown in Table 3-2, and sized as required to comply with
local and National electrical codes.
Table 3-2 AC Connection Specifications
Material XGI 1500-125/125
XGI 1500-125/150
XGI 1500-150/166
XGI 1500-166/166
AC Output
(L1, L2, L3)
Conductors
Copper
Aluminum
1 AWG to 500 kcmil
(42.4 to 240 mm
2
)
2/0 AWG to 500 kcmil
(67.4 to 240 mm
2
)
1/0 AWG to 500 kcmil
(53.5 to 240 mm
2
)
3/0 AWG to 500 kcmil
(85.0 to 240 mm
2
)
2/0 AWG to 500 kcmil
(67.4 to 240 mm
2
)
4/0 AWG to 500 kcmil
(107 to 240 mm
2
)
2/0 AWG to 500 kcmil
(67.4 to 240 mm
2
)
4/0 AWG to 500 kcmil
(107 to 240 mm
2
)
Neutral
(Bonded to
Ground)
Copper
Aluminum
4 to 1/0 AWG
(21.1 to 53.5 mm
2
)
2 to 1/0 AWG
(33.6 to 53.5 mm
2
)
4 to 1/0 AWG
(21.1 to 53.5 mm
2
)
2 to 1/0 AWG
(33.6 to 53.5 mm
2
)
4 to 1/0 AWG
(21.1 to 53.5 mm
2
)
2 to 1/0 AWG
(33.6 to 53.5 mm
2
)
4 to 1/0 AWG
(21.1 to 53.5 mm
2
)
2 to 1/0 AWG
(33.6 to 53.5 mm
2
)
Electric Shock Hazard
Components with hazardous voltage and energy will electrocute the operator.
Ensure AC power doesn’t flow into inverter. Verify with a multimeter.
Turn the AC Switch OFF before wiring. Wire the AC Connections as shown in Figure 3-15.
For the AC connections, use compression lugs with a single hole for a ½ in or M12 stud and sized for the wire
gauge used. The width of the lugs must be 1.5 in (38 mm) or less. Torque to 220 in-lbs (25 N-m) using an
18mm socket and torque driver. A hex nut and washer are provided. The terminal block accepts single or
parallel conductor sets. See Figure 3-17 for the hardware assembly instructions.
Although a neutral terminal is available, a neutral conductor is not required for inverter operation. The neutral
terminal is bonded to chassis and only used for voltage sensing. If a neutral conductor is installed, torque the
neutral terminal based on the conductor size according to Error! Reference source not found. using either
3/16 Allen hex key or a slot torque driver.
Table 3-3 Neutral Terminal Torque Specifications
(42.3 mm
2
)
(42.4 to 53.5 mm
2
)
Neutral
50 in-lbs
(5.6 N-m)
55 in-lbs
(6.2 N-m)