EasyManua.ls Logo

YASKAWA SOLECTRIA XGI 1500 Series - DC Connection Using the XGI Attachable Combiner Box

YASKAWA SOLECTRIA XGI 1500 Series
77 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and Operation Guide SOLECTRIA XGI 1500 (Rev A, April 2019)
26 of 77
DC Connection Using the XGI Attachable Combiner Box
3.10
Figure 3-18 XGI 1500V with Attachable Combiner Box Option
Electric Shock Hazard
Components with hazardous voltage and energy pose the risk of electrocuting operators.
Verify the absence of DC voltage and current.
Turn DC Disconnect to OFF
Verify the absence of DC voltage and current.
Check Polarity of DC Inputs
DC inputs with the wrong polarity may cause damage to inverter.
Confirm proper polarity of connections with a multimeter.
The PV Output Circuit Wiring Harness Assembly is designed to simplify the field interconnection of the
Combiner and the XGI 1500 inverter. The Wiring Harness Assembly comprises:
A straight section of 1.5-inch PVC about 7-inches in length, with 90-degree elbows and
threaded couplings at each end
Two (2) 250 kcmil conductors for the PV Output Circuit overall positive (red) and overall
negative (black), with lugs crimped on the ends of the wires to facilitate termination on posts in
the Combiner and the XGI 1500 inverter, and
A 4AWG green equipment ground wire, with stripped ends for easy termination at the busbars in
the Combiner and XGI 1500 inverter.