Installation and Operation Guide SOLECTRIA XGI 1500 (Rev A, April 2019)
24 of 77
3.8.3 Fuses Configuration and Sizes
Refer to Table 3-6 for information regarding fuse sizes and configuration.
Table 3-6 Attachable Combiner Box
Number of DC Inputs 16, 20, 24, 26, 28
Fuse Rating Options
15 A, 20 A (16, 20, 24, 26 or 28 positions)
25 A (20 positions), 30 A (16 positions)
Fuse Configuration Both Poles Fused
Switch Configuration Both Poles Switched
Open Fuse Holders
Verify the absence of DC voltage and current when inserting or removing fuses.
Use Correct Fuses
Size the fuses following NEC requirements.
DC Connection Using the XGI Remote or Attachable Combiner