8.3 Voltage and Frequency Limits and Trip Times
All models of the SOLECTRIA XGI 1500 comply with IEEE1547-2003 requirements. The tables below show its
standard settings.
Table 8-3 Default Voltage Limits and Trip Times
Voltage Range (± 1%) Clearing Time (± 0.2 s)
and Including (± 0.1 s)
V < 45% 0.16 s
0.16 s
45% <= V < 60% 1.0 s
11 s
60% <= V < 88% 2.0 s
21 s
88% <= V < 110% No trip
No trip
110% <= V <= 120% 1.0 s
13 s
f > 120% 0.16 s
0.16 s
Table 8-4 Frequency Limits and Trip Times
Frequency Range (± 0.05 Hz) Clearing Time (± 0.2 s)
Clearing Time Adjustable Up to
and Including (± 0.1 s)
F < 57 Hz 0.16 s
10 s
57 Hz <= F < 59.5 Hz 2.0 s
300 s
59.5 Hz <= F < 60.5 Hz No trip
No trip
60.5 Hz <= F <= 62 Hz 2.0 s
300 s
V > 62 Hz 0.16 s
10 s
Figure 8-1 Derating with AC Voltage