Installation and Operation Guide SOLECTRIA XGI 1500 (Rev A, April 2019)
70 of 77
8.3 Voltage and Frequency Limits and Trip Times
All models of the SOLECTRIA XGI 1500 comply with IEEE1547-2003 requirements. The tables below show its
standard settings.
Table 8-3 Default Voltage Limits and Trip Times
Voltage Range (± 1%) Clearing Time (± 0.2 s)
Clearing
Time Adjustable Up to
and Including (± 0.1 s)
V < 45% 0.16 s
0.16 s
45% <= V < 60% 1.0 s
11 s
60% <= V < 88% 2.0 s
21 s
88% <= V < 110% No trip
No trip
110% <= V <= 120% 1.0 s
13 s
f > 120% 0.16 s
0.16 s
Table 8-4 Frequency Limits and Trip Times
Frequency Range (± 0.05 Hz) Clearing Time (± 0.2 s)
Clearing Time Adjustable Up to
and Including (± 0.1 s)
F < 57 Hz 0.16 s
10 s
57 Hz <= F < 59.5 Hz 2.0 s
300 s
59.5 Hz <= F < 60.5 Hz No trip
No trip
60.5 Hz <= F <= 62 Hz 2.0 s
300 s
V > 62 Hz 0.16 s
10 s
Figure 8-1 Derating with AC Voltage