7 Troubleshooting
YASKAWA Europe TOEP C710606 101A - V1000 MMD IP65 Motor Mounted Drive - Quick Start Guide EN 47
ENGLISH
STO Errors
LED Operator
Display
Cause Corrective Action
STO
The wrong motor code has been set (Yaskawa
motors only).
Enter the correct motor code for the PM being
used into E5-01.
For special purpose motors, enter the correct data
provided for the motor into E5- parameters
according to the test report provided for the mon-
itor.
Load is too heavy.
Increase the value set to n8-55 (Load Inertia for
PM).
Increase the value set to n8-51 (Pull-in Current
during Accel/Decel for PM.
Reduce the load.
Increase the motor or drive capacity.
Load inertia is too heavy.
Increase n8-55 (Load Inertia for PM).
Acceleration and deceleration times are
too short.
Increase the acceleration and deceleration times
(C1-01 through C1-08).
Increase the S-curve acceleration and decelera-
tion times (C2-01).
WWW.NNC.IR

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 MMD and is the answer not in the manual?

YASKAWA V1000 MMD Specifications

General IconGeneral
SeriesV1000
ModelMMD
Input Voltage200-240 VAC, 380-480 VAC
Output Power0.4 kW to 315 kW
Control MethodV/f control
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short circuit

Related product manuals