8 Object Description
YASKAWA ELECTRIC SIEP C730600 24A V1000 Option CANopen Technical Manual 19
Store Parameters
By writing "SAVE" (s = 73H, a = 61H, v = 76H, e = 65H) into this object, the SI-S3/V settings are saved in the non-volatile memory. The SI-S3/V
will operate using these settings when a Reset Node or Reset Communications command was performed or when the power supply was cycled.
Restore Default Parameter
Writing "LOAD" (l = 6CH, o = 6FH, a = 61H, d = 64H) into this object restores the SI-S3/V default settings.
COB-ID Emergency Object
This object defines the COB-ID of the emergency object.
Consumer Heartbeat Time
This object defines the Consumer heartbeat time. It must be set to a higher value than the producer heartbeat time set in the master. When set to 0,
consumer heartbeat is disabled.
Producer Heartbeat Time
This object determines the cycle time the SI-S3/V uses to produce a heartbeat signal. When set to 0, the SI-S3/V does not produce a heartbeat signal.
Identity Object
This object contains general information about the drive.
Manufacturer Specific Objects
Operation Command
This object is used to operate the drive, set digital inputs and to trigger or reset a drive fault.
Speed Command
Sets the frequency reference. The unit of this value depends on the setting of the drive parameter o1-03.
Torque Limit
This object sets the torque limit in units of 0.1%. It can be used in Open Loop Vector control only.
Index (Hex.) Subindex Content Access PDO Mapping Value Range
1010 1 Store Parameters Read / Write No Unsigned 32
Index (Hex.) Subindex Content Access PDO Mapping Value Range
1011 1 Restore Default Parameters Read / Write No Unsigned 32
Index (Hex.) Subindex Content Access PDO Mapping Value Range
1014 COB-ID Emergency Object Read Only No Unsigned 32
Index (Hex.) Subindex Content Access PDO Mapping Value Range Units
1016 1 Consumer Heartbeat Time Read / Write No Unsigned 32 1 ms
Index (Hex.) Subindex Content Access PDO Mapping Value Range Units
1017 Producer Heartbeat Time Read / Write No Unsigned 32 1 ms
Index (Hex.) Subindex Content Access PDO Mapping Value Range
1018 Identity Object Read Only No Unsigned 32
Index (Hex.) Subindex Content Access PDO Mapping Data Length
2000 0 Operation Commands Read / Write Possible 2 byte
Bit No Description Function
0 Forward Run
Effective when Run command source is set to option unit
(b1-02/16=3)
1 Reverse Run
Effective when Run command source is set to option unit
(b1-02/16=3)
2 Terminal S3 enable/disable Depends on H1-03 setting
3 Terminal S4 enable/disable Depends on H1-04 setting
4 Terminal S5 enable/disable Depends on H1-05 setting
5 Terminal S6 enable/disable Depends on H1-06 setting
6 Terminal S7 enable/disable Depends on H1-07 setting
7 Not used
8 External Fault (EF0)
9 Fault Reset
A to F Not used
Index (Hex.) Subindex Content Access PDO Mapping Data Length
2010 0 Speed Command Read / Write Possible 2 byte
Index (Hex.) Subindex Content Access PDO Mapping Data Length
2020 0 Torque Limit Read / Write Possible 2 byte