8 Object Description
YASKAWA ELECTRIC SIEP C730600 24A V1000 Option CANopen Technical Manual 21
Output Frequency
This object can be used to read out the drive output frequency. The unit of this value depends on the setting of drive parameter o1-03.
Output Current
This object can be used to read out the drive output current. Units are determined by parameter o1-03.
Output Torque
This object can be used to read out the drive output torque. It can be used in Open Loop Vector control only.
MEMOBUS Read Response
This object contains the data of the drive MEMOBUS register specified in object 2040 (Hex.).
MEMOBUS Write Response
MEMOBUS Not Limited Enter Command Response
Motor Speed
Monitors the value of the motor speed. The unit of this value depends on the setting of drive parameter o1-03. The register content is zero if the
drive is set for V/f control.
Drive and Motion Control (DSP402)
Digital Input
This object contains the drive digital output status (seen as input to the network).
Digital Output
This object is used to set drive digital inputs (seen as output from the network).
Index (Hex.) Subindex Content Access PDO Mapping Data Length
2110 0 Output Frequency Read Only Possible 2 byte
Index (Hex.) Subindex Content Access PDO Mapping Data Length
2120 0 Output Current Read Only Possible 2 byte
Index (Hex.) Subindex Content Access PDO Mapping Data Length
2130 0 Output Torque Read Only Possible 2 byte
Index (Hex.) Subindex Content Access PDO Mapping Data Length
2140
0 Number of Entries
Read Only Possible
1 byte
1 MEMOBUS Read Response
2 + 2 byte
MEMOBUS Address + 00H
Index (Hex.) Subindex Content Access PDO Mapping Data Length
2150
0 Number of Entries
Read Only Possible
1 byte
1 MEMOBUS Write Response
2 + 2 byte
MEMOBUS Address + Data
Index (Hex.) Subindex Content Access PDO Mapping Data Length
2160 0
MEMOBUS Not Limited Enter Command
Response
Read Only Possible 4 byte
Index (Hex.) Subindex Content Access PDO Mapping Data Length
2200 0 Motor Speed Read Only Possible 4 byte
Index (Hex.) Subindex Content Access PDO Mapping Value Range
60FD Drive Digital Output Status Read Only Possible
0...(2
32
-1)
Bit No Description
0 to F Not used
10 Terminal MA-MB-MC Output
11 Terminal P1-PC Output
12 Terminal P2-PC Output
13 to 1F Not used
Index (Hex.) Subindex Content Access PDO Mapping Value Range
60FE Drive Digital Input Command Read / Write Possible
0...(2
32
-1)
Bit No Description Function
0 to 11 Not used
12 Terminal S3 enable/disable Depends on H1-03 setting
13 Terminal S4 enable/disable Depends on H1-04 setting
14 Terminal S5 enable/disable Depends on H1-05 setting
15 Terminal S6 enable/disable Depends on H1-06 setting
16 Terminal S7 enable/disable Depends on H1-07 setting