■ Instrument Input Range Codes
Input Type
Instrument Input
Range Code
Instrument
Input Range
Measurement Accuracy
OFF
1
-270.0 to 1370.0°C
-450.0 to 2500.0°F
Set the data item PV Input Type “IN1” to the OFF option to leave the PV input
type undefined.
2
-270.0 to 1000.0°C
-450.0 to 2300.0°F
K
-200.0 to 500.0°C
-200.0 to 1000.0°F
J
4
-200.0 to 1200.0°C
-300.0 to 2300.0°F
5
-270.0 to 400.0°C
-450.0 to 750.0°F
T
6
-000.0 to 400.0°C
-200.0 to 750.0°F
0.1% of instrument range 1 digit at 0°C or more
0.2% 1 digit for temperatures below 0°C,
where the accuracy is: 2% of instrument range 1
digit for temperatures below -200.0°C for a type-K
thermocouple, or 1% of instrument range 1 digit for
temperatures below -200.0°C for a type-T thermocouple.
B7
-000.0 to 1800.0°C
-032.0 to 3300°F
0.15% of instrument range 1 digit at 400°C or more
5% of instrument range 1 digit at less than 400°C
S8
-000.0 to 1700.0°C
-032.0 to 3100°F
R9
-000.0 to 1700.0°C
-032.0 to 3100°F
0.15% of instrument range 1 digit
N10
-200.0 to 1300.0°C
-300.0 to 2400.0°F
0.1% of instrument range 1 digit
0.25% of instrument range 1 digit for temperatures
below 0°C
E11
-270.0 to 1000.0°C
-450.0 to 1800.0°F
L(DIN) 12
-200.0 to 900.0°C
-300.0 to 1600.0°F
-200.0 to 400.0°C
-300.0 to 750.0°F
13
U(DIN)
14
-000.0 to 400.0°C
-200.0 to 1000.0°F
0.1% of instrument range 1 digit at 0°C or more
0.2% 1 digit for temperatures below 0°C, where the
accuracy is:1.5% of instrument range 1 digit for
temperatures below -200.0°C for a type-E thermocouple.
W15
-000.0 to 2300.0°C
-032.0 to 4200°F
0.2% of instrument range 1 digit
Platinel 2 16
-000.0 to 1390.0°C
-032.0 to 2500.0°F
0.1% of instrument range 1 digit
PR20-40 17
-000.0 to 1900.0°C
-032.0 to 3400°F
0.5% of instrument range 1 digit at 800°C or more
No accuracy is guaranteed at less than 800°C
Thermocouple
Unspecified
W97Re3-
W75Re25
18
-000.0 to 2000.0°C
-032.0 to 3600°F
0.2% of instrument range 1 digit
30
-200.0 to 500.0°C
-300.0 to 1000.0°F
0.1% of instrument range 1 digit (Note 1) (Note 2)
JPt100
31
-150.00 to 150.00°C
-200.0 to 300.0°F
0.2% of instrument range 1 digit (Note 1)
35
-200.0 to 850.0°C
-300.0 to 1560.0°F
36
-200.0 to 500.0°C
-300.0 to 1000.0°F
0.1% of instrument range 1 digit (Note 1) (Note 2)
RTD
Pt100
37
-150.00 to 150.00°C
0-200.0 to 300.0°F
0.2% of instrument range 1 digit (Note 1)
0.4 to 2 V
40
Standard
signal
1 to 5 V 41
0 to 2 V 50
0 to 10 V 51
0.400 to 2.000 V
1.000 to 5.000 V
0.000 to 2.000 V
0.00 to 10.00 V
-10 to 20 mV
55 -10.00 to 20.00 mV
DC voltage
0 to 100 mV
56 0.0 to 100.0 mV
0.1% of instrument range 1 digit
Display range is scalable in a range of -19999 to 30000.
Display span is 30000 or less.
3
* Performance in the standard operating conditions (at 23±2˚C, 55±10%RH, and 50/60 Hz power frequency)
Note 1: The accuracy is ±0.3˚C of instrument range ±1 digit for a temperature range from 0˚C to 100˚C.
Note 2: The accuracy is ±0.5˚C of instrument range ±1 digit for a temperature range from -100˚C to 200˚C.
* To receive a 4-20 mA DC signal, select a standard signal of 1 to 5 V DC and connect it to a 250 resistor. This resistor
is optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)