7-4
IM 01C50C05-01EN
Input entity parameters: Ui(Vmax)=30V, Ii(I max)=120mA, Pi=0.84W,
Ci=1nF, Li=10
μ
H
Output entity parameters: Uo(Uoc)=9.6V, Io(Isc)=28mA,
Po(Pmax)=67.2mW, Co(Ca)=3.5
μ
F, Lo(La)=35mH
7.3 EMC Conformity
EN 61326-1 Class A, Table2
EN 61326-2-3
CAUTION
This instrument is a Class A product, and it is designed for use in the
industrial environment. Please use this instrument in the industrial
environment only.
7.4 EURoHSDirective
Applicable standard: EN IEC 63000
Applicable production sites are shown below
The condition of the RoHS compliant production site are as follows:
Singapore, China
The production sites can be conrmed by the serial number shown in the
frame of “No.” in the name plate of the product.
Serial numbers (9 letters): AAnnnnnnn
AA: Identication code of production site
Singapore: Use “C2” or “C0” China: Use “S5”