8-13
IM 01C50C05-01EN
Burst Parameters
Command
Parameter
Burst Command
Burst Msg
Trigger Mode
Burst Trigger
Source
Burst Trigger
Units
PV
Temperature
value assigned
to PV
Cmd1: PV Continuous - -
Window PV Depend on PV
assignment
Rising
Falling
On-change
% range/Loop
current
Cmd2: % range/
Current
Continuous - -
Window % range %
Rising
Falling
On-change
Process
variables/Loop
current
Cmd3: Dyanamic
variables/Current
Continuous - -
Window PV Depend on PV
assignment
Rising
Falling
On-change
Process vars/%
range/Loop
current with
status
Cmd9: Device
variables with
status
Continuous - -
Window Sensor, El/CJC,
PV, SV, TV,
QV(*1)
Depend on
burst trigger
source
Rising
Falling
On-change
Process vars/%
range/Loop
Current
Cmd33: Device
variables
Continuous - -
Window Sensor, El/CJC,
PV, SV, TV,
QV(*1)
Depend on
burst trigger
source
Rising
Falling
On-change
Self diagnosis
information
Cmd48: Additional
device status
Continuous - -
(*1) Loop current and % range are selectable from menu but not available.