SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
Decrease
Access Level Required: SERVICE
Pressing this button will set the selected device’s state
to Manual if it had been in Auto and will decrease the
device’s present control command by an amount equal
to the Manual Increment.
Set
Access Level Required: SERVICE
Pressing this button will open a dialog box where the
user can manually enter a command value for the se-
lected device. Once a legitimate value has been entered
and the Enter key pressed, the Selected device’s state
shall be set to Manual if it had been in Auto and the
Selected device’s control command shall be set to the
entered value.
Auto
Access Level Required: SERVICE
Pressing this button will set the selected device’s con-
trol state to Auto. This button shall only be shown when
the selected device’s state is Manual.
NAVIGATION
Home
Causes and instant return to the Home Screen.
Compressor
Causes an instant navigation to the Compressor Screen.
VSD
Causes an instant navigation to the VSD Screen.
Setpoints
Access Level Required: SERVICE
Moves to the Capacity Control Setpoints subscreen
that allows the Service Technician to verify and edit
values significant to capacity control. This button will
only be shown and enabled when the Access Level is
Service or greater. Service Technicians refer to YORK
YMC
2
Service Manual (Form 160.78-M2).