JOHNSON CONTROLS
157
SECTION 3 - PRINTERS
FORM 160.67-O1
ISSUE DATE: 4/1/2015
3
FIGURE 56 – SAMPLE PRINTOUT (SETPOINTS) (CONT’D)
Speed Setpoints
-------------------------------------------------------
SSP1 - Slow Roll Speed = 1000 RPM
SSP2 - Minimum Rated Speed = 3200 RPM
SSP3 - Fixed Speed = 4200 RPM
SSP4 - Overspeed Test Limit = 5000 RPM
SSP5 - Chilled Liquid Pump Turn-On Speed = 1200 RPM
SSP7 - Turbine Auxiliary Oil Pump Activate = 3000 RPM
SSP8 - OverSpeed Shutdown = 4900 RPM
SSP9 - Maximum Rated Speed = 4500 RPM
SSP10 - Maximum Speed Analog Input = 5000 RPM
Time Setpoints
--------------------------------------------------------
TDSP1 - Excessive Slow Roll Timeout = 1200 Sec
TDSP2 - Turbine Nozzle Solenoid #1 Delay = 300 Sec
TDSP3 - Turbine Nozzle Solenoid #2 Delay = 100 Sec
TDSP4 - Chilled Liquid Pump Turn-On Delay = 2 Sec
TDSP5 - Chilled Liquid Flow Switch Check Dela = 10 Sec
TDSP6 - Subcooler Level Valve Pulldown Delay = 10 Min
TDSP7 - Turbine Exhaust Steam High Pressure T = 600 Sec
TDSP8 - Excessive Start Delay Timeout = 1200 Sec
TDSP9 - Soft Shutdown Rampdown Timeout = 10 Min
TDSP10 - Temp Control Override Transfer Delay = 5 Sec
TDSP11 - Hotwell Pump Shutdown Delay = 360 Sec
TDSP12 - Turbine Auxiliary Oil Pump Postlube = 30 Min
TDSP13 - Hotwell High Level Timeout = 10 Sec
TDSP14 - AntiSurge Update Delay Time = 30 Sec
TDSP15 - Turbine Mechanical Trip Timeout = 5 Sec
TDSP16 - Slow Roll Underspeed Timeout = 100 Sec
TDSP17 - Turbine Stabilization Delay = 120 Sec
Temperature Setpoints
--------------------------------------------------------
TSP3 - Hot Gas Valve Temp Controller Diff. = 1.1 ~F
TSP4 - Turbine Shaft End Bearing Warning = 210.0 ~F
TSP5 - Turbine Shaft End Bearing Shutdown = 219.9 ~F
TSP6 - Turbine Governor End Bearing Warning = 210.0 ~F
TSP7 - Turbine Governor End Bearing Shutdown = 219.9 ~F
TSP8 - Turbine Supply Oil Warning = 129.9 ~F
TSP9 - Turbine Supply Oil Shutdown = 135.0 ~F
Vibration
-------------------------------------------------------
TVSP1 - Turbine Shaft Vibration Warning = 3.0 Mils
TVSP2 - Turbine Shaft Vibration Shutdown = 3.0 Mils
Flow Sensor
--------------------------------------------------------
FSE1 - Steam Flow Sensor Enable = Disabled
FSP1 - Steam Flow Sensor Range = 24000 Lb/Hr
FSP4 - Steam Flow Transmitter Signal Type = Linear
FSE2 - Evaporator Flow Sensor Enable = Enabled
FSP2 - Evaporator Flow Sensor Range = 6000 Gal/Min
FSP5 - Evaporator Flow Transmitter Signal Typ = Linear
FSE3 - Condenser Flow Sensor Enable = Enabled
FSP3 - Condenser Flow Sensor Range = 8000 Gal/Min
FSP6 - Condenser Flow Transmitter Signal Type = Linear
Temperature Controller PID
-------------------------------------------------------
TSP1 - Leaving Chilled Local Setpoint = 42.1 ~F
Temperature Controller - HGV: Proportional = 1.00
Temperature Controller - HGV: Integral = 5.00
Temperature Controller - HGV: Derivative = 0.00
Temperature Controller - PRV: Proportional = 1.00
Temperature Controller - PRV: Integral = 5.00
Temperature Controller - PRV: Derivative = 0.00
Temperature Controller - SPD: Proportional = 1.00
Temperature Controller - SPD: Integral = 5.00
Temperature Controller - SPD: Derivative = 0.00
Evaporator PID
-------------------------------------------------------
PSP1 - Evaporator Pressure Controller = 30.0 Psig
Evaporator - HGV: Proportional = 1.00
Evaporator - HGV: Integral = 5.00
Evaporator - HGV: Derivative = 0.00
Evaporator - PRV: Proportional = 1.00
Evaporator - PRV: Integral = 5.00
Evaporator - PRV: Derivative = 0.00
Evaporator - SPD: Proportional = 1.00
Evaporator - SPD: Integral = 5.00
Evaporator - SPD: Derivative = 0.00
Condenser PID
-------------------------------------------------------
PSP2 - Condenser Pressure Controller = 145.0 Psig
Condenser - HGV: Proportional = 1.00
Condenser - HGV: Integral = 5.00
Condenser - HGV: Derivative = 0.00
Condenser - PRV: Proportional = 1.00
Condenser - PRV: Integral = 5.00
Condenser - PRV: Derivative = 0.00
Condenser - SPD: Proportional = 1.00
Condenser - SPD: Integral = 5.00
Condenser - SPD: Derivative = 0.00
Hotwell Level PID
-------------------------------------------------------
HLSP1 - Hotwell Condensate Level = 50.0 %
Hotwell Level: Proportional = 5.00
Hotwell Level: Integral = 0.00
Hotwell Level: Derivative = 0.00
Hotwell Level: Offset = 50.0 %
Subcooler Level PID
-------------------------------------------------------
LSP1 - Subcooler Refrigerant Level = 50 %
Subcooler Level: Proportional = 1.00
Subcooler Level: Integral = 5.00
Subcooler Level: Derivative = 0.00
Governor PID
-------------------------------------------------------
Governor Slow Roll Speed: Proportional = 1.00
Governor Slow Roll Speed: Integral = 5.00
Governor Slow Roll Speed: Derivative = 0.00
Governor Min Rated Speed: Proportional = 1.00
Governor Min Rated Speed: Integral = 5.00
Governor Min Rated Speed: Derivative = 0.00
Governor Rated Speed: Proportional = 1.00
Governor Rated Speed: Integral = 5.00
Governor Rated Speed: Derivative = 0.00
Governor Position Limit PID
-------------------------------------------------------
GSP1 - Power Limiting Governor Position = 100.0 %
Governor Valve Position: Proportional = 1.00
Governor Valve Position: Integral = 5.00
Governor Valve Position: Derivative = 0.00
First Stage Pressure Limit PID
-------------------------------------------------------
PSP3 - Power Limiting Turbine First Stage Pre=60.0 Psig
First Stage Pressure: Proportional = 1.00
First Stage Pressure: Integral = 5.00
First Stage Pressure: Derivative = 0.00