JOHNSON CONTROLS
68
FORM 160.67-O1 
ISSUE DATE: 4/1/2015
SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
PROGRAMMABLE/DISPLAY ONLY
Governor (Min Rated)
Screen:  Capacity Controls
SP (SSP2) Range: 3200-3600 RPM SP (SSP2) Default: 3200 RPM
RR (RRSP4) Range: 100-200 RPM/Sec RR (RRSP4) Default: 200 RPM/Sec 
PID Tuning Ranges - P: 0.00-5.00 I: 0.00-5.00 D: 0.00-5.00 
PID Tuning Defaults -  P: 0.75 I: 2.00  D: 0.00
This box displays parameters pertinent to the Gover-
nor (Speed Control) PID Logic during the ramp up to 
rated speed to maintain the speed (PV) at the setpoint 
(SP). The output (CV) displayed will decrease to close 
the governor valve if the speed increases above the 
setpoint. The setpoint is automatically ramped from 
the SSP1- Slow Roll Speed to the SSP3 – Fixed Speed 
shown on the Speed Setpoints Screen at the ramp rate 
(RR) shown as long as the Speed Setpoint is in the Auto 
mode. The green Auto text changes to yellow Manual 
text to show the status of the Speed Setpoint as pres-
ently selected on the Auto/Manual Screen.  
Governor (Rated) 
Screen:  Capacity Controls
SP Range: 3200-4700 RPM SP Default: 4500 RPM
RR (RRSP4) Range: 1-200 RPM/Sec RR (RRSP4) Default: 10 RPM/Sec 
PID Tuning Ranges - P: 0.00-5.00 I: 0.00-5.00 D: 0.00-5.00 
PID Tuning Defaults -  P: 1.20 I: 1.21  D: 0.00
This box displays parameters pertinent to the Gover-
nor (Speed Control) PID Logic during normal opera-
tion at the minimum rated speed or above to maintain 
the speed (PV) at the setpoint (SP). The output (CV) 
displayed will decrease to close the governor valve if 
the speed increases above the setpoint. The setpoint is 
automatically ramped to the setpoint dictated by the 
capacity/anti-surge controls after the turbine stabiliza-
tion period at the ramp rate (RR) shown as long as the 
Speed Setpoint is in the Auto mode and will never be 
allowed drop below SSP2-Minimum Rated Speed nor 
rise above SSP9-Maximum Rated Speed shown on the 
Speed Setpoints Screen. The green text shows the Auto 
or Manual status of the Speed Setpoint as presently se-
lected on the Auto/Manual Screen.
Gov Valve Position Limit 
Screen:  Capacity Controls
SP (GSP1) Range: 20.0-100.0 %  SP (GSP1) Default: 100.0 %
PID Tuning Ranges - P: 0.00-5.00 I: 0.00-5.00 D: 0.00-5.00 
PID Tuning Defaults -  P: 1.00 I: 1.50  D: 0.00
This box displays parameters pertinent to the Governor 
Valve Position Limit power limiting override control-
ler which is active only when MSSP8-Power Limiting 
Mode on Capacity Control Setpoints Screen 1 is set for 
Position. The output (CV) displayed will decrease to 
reduce the speed setpoint, close the vanes, and open the 
hot gas valve if required to maintain the governor valve 
output signal (PV) at the setpoint (SP). The setpoint is 
usually determined by observing the Governor Valve 
output signal at normal full load conditions and then 
entering this percent as the setpoint of this control-
ler. The green Inactive text changes to yellow Active 
to display if the controller is presently controlling the 
chiller capacity.
Horsepower Limit 
Screen:  Capacity Controls
SP (HLSP) Range: Variable SP  Default: 840
PID Tuning Ranges - P: 0.00-5.00 I: 0.00-5.00 D: 0.00-5.00 
PID Tuning Defaults -  P: 1.00 I: 1.50  D: 0.00
This box displays parameters pertinent to the Horse-
power Limit override controller which is active only 
when MSSP8-Power Limiting Mode on Capacity Con-
trol Setpoints Screen 1 is set for Horepower. The out-
put (CV) displayed will decrease to reduce the speed 
setpoint, close the vanes, and open the hot gas valve 
if required to maintain the turbine horsepower (PV) at 
the setpoint (SP). The horsepower setpoint is initially 
set to the maximum allowable based on the compres-
sor model entered on the Setup Screen. It is factory 
adjusted to the lower of the compressor maximum or 
115% of the turbine design horsepower and can only 
be changed in the TEST OP or ADMIN ACCESS level. 
The turbine horsepower (PV) is automatically calcu-
lated by the program based on the inlet, first stage, and 
exhaust steam conditions. The green text changes to 
Inactive or Active to display if the controller is pres-
ently controlling the chiller capacity.