Page – 48/139 AFFZP0BB – ACE3 – User Manual
SET OPTIONS
Parameter Allowable range Description
MAIN POT. TYPE
(T, TM)
0 ÷ 11 This parameter defines the type of the main potentiometer
connected to A3 contact.
0: V-type pot, low to high value, with direction switches,
without enable switch, without enable dead band.
1: V-type pot, low to high value, with direction switches,
without enable switch, with enable dead band.
2: V-type pot, high to low value, with direction switches,
without enable switch, without enable dead band.
3: V-type pot, high to low value, with direction switches,
without enable switch, with enable dead band.
4: Z-type pot, low to high value, with direction switches,
without enable switch, without enable dead band.
5: Z-type pot, low to high value, with direction switches,
without enable switch, with enable dead band.
6: Z-type pot, low to high value, without direction switches,
with enable switch, with enable dead band
7: Z-type pot, low to high value, without direction switches,
without enable switch, with enable dead band.
8: Z-type pot, high to low value, with direction switches,
without enable switch, without enable dead band.
9: Z-type pot, high to low value, with direction switches,
without enable switch, with enable dead band.
10: Z-type pot, high to low value, without direction
switches, with enable switch, with enable dead band.
11: Z-type pot, high to low value, without direction
switches, without enable switch, with enable dead band.
AUX POT. TYPE
(T, TM, TS, P)
0 ÷ 15 This parameter defines the type of the auxiliary potentiometer
connected to A10 contact.
0 ÷ 11: Same as MAIN POT. TYPE, see prev. parameter.
12: No pot, with direction switches, with enable switch
15: No pot, with direction switches, without enable switch
SET MOT.TEMPERAT
(T, TM, P, CO)
NONE ÷ OPTION#3 This parameter defines the type of motor temperature sensor
adopted.
NONE = no motor thermal sensor is connected.
DIGITAL = a digital (ON/OFF) motor thermal sensor is
connected to A23.
OPTION#1 = an analog motor thermal sensor is connected
to A23. The temperature sensor is a KTY 84-130 PTC
(positive thermal coefficient resistance).
OPTION#2 = an analog motor thermal sensor is connected
to A23. The temperature sensor is a KTY 83-130 PTC
(positive thermal coefficient resistance)
OPTION#3 = an analog motor thermal sensor is connected
to A23. The temperature sensor is a PT1000 PTC (positive
thermal coefficient resistance).