104
2600T SERIES |  PRESSURE TRANSMITTERS |  OI/266/FF-EN REV. E
Block Mapping
Idx Parameter Description / Range / Selections / Note
 BLOCK_OBJ
In the Block Object data structure, there are different items describing the block characteristics. Execution period, Number 
of parameters in the block, the DD Revision, Profile Revision, View Objects characteristics and so on  
 ST_REV
The revision level of the Static data associated with the Function Block. The revision level is incremented each time a static 
parameter value (S – under Storage) in the block is changed. 
 TAG_DESC The user description of the intended application of the block
 STRATEGY The strategy field can be used to identify grouping of blocks. This data is not checked or processed by the block.
 ALERT_KEY The identification number of the plant unit. This information may be used in the host for sorting alarms, etc.
 MODE_BLK
TARGET AUTO / MAN / OOS The selectable modes by the operator.
ACTUAL The mode the block is currently in. 
PERMITTED AUTO / MAN / OOS  Allowed modes that the target may take on
NORMAL AUTO The common mode for the Actual.
 BLOCK_ERR
This parameter reflects the error status associated with the hardware or software components associated with a block. It 
is a bit string, so that multiple errors may be shown. 
 OUT The block output value calculated as a result of the 
block execution, expressed in OUT_SCALE unit
Writeable only if MODE_BLK.ACTUAL = MAN
 OUT_SCALE
The high and low scale values, engineering units code, and number of digits to the right of the decimal point to be used in 
displaying the OUT parameter and parameters which have the same scaling as OUT.
 GRANT_DENY
 STATUS_OPTS
Options which the user can select for the block processing of status. The available selections are:
 IFS if BAD IN
 Use Uncertain as Good
  First input value to the selector
Expressed in OUT_SCALE Unit  Second input value to the selector
  Third input value to the selector
 SEL_TYPE
This parameter specifies the type of selector action 
Low
High
Middle
 BKCAL_IN
The analog input value from another block’s BKCAL_OUT output that is used to prevent reset windup and to initialize the 
control loop. Expressed in OUT_SCALE Unit
 OUT_HI_LIM
Expressed in OUT_SCALE Unit
Limits the maximum output value.
 OUT_LO_LIM Limits the minimum output value.
 
 
 
 UPDATE_ EVT This alert is generated by any change to the static data
 BLOCK_ALM
The block alarm is used for all configuration, hardware, connection failure or system problems in the block. The cause of the 
alert is entered in the subcode field. The alert will set the Active Status in the status parameter. When the Unreported 
status is cleared by the alert reporting task, another block alert may be reported without clearing the Active Status, if the 
subcode has changed