2600T SERIES | PRESSURE TRANSMITTERS | OI/266/FF-EN REV. E
Range & Span consideration
The 2600T Transmitter Specification Sheets provide all information concerning the Range and Span limits in relation to the model
and the sensor code.
The terminology currently used to define the various parameters is as follows:
URL: Upper Range Limit of a specific sensor. The highest value of the measured value that the transmitter can be adjusted to
measure.
LRL: Lower Range Limit of a specific sensor. The lowest value of the measured value that the transmitter can be adjusted to
measure.
URV: Upper Range Value. The highest value of the measured value to which the transmitter is calibrated.
LRV: Lower Range Value. The lowest value of the measured value to which the transmitter is calibrated.
SPAN: The algebraic difference between the Upper and Lower Range Values. The minimum span (MIN SPAN) is the minimum value
that can be used without degradation of the specified performance. The calibration span (CAL SPAN) is the difference between
Upper Range Value (URV) and Lower Range Value (LRV).
TD: (or Turn Down Ratio) is the ratio between the maximum span and the calibrated span.
The transmitter can be calibrated with any range between the LRL and the URL with the following limitations:
LRL LRV (URL - CAL SPAN)
CAL SPAN MIN SPAN
URV URL

Table of Contents

Other manuals for ABB 2600T Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB 2600T Series and is the answer not in the manual?

ABB 2600T Series Specifications

General IconGeneral
BrandABB
Model2600T Series
CategoryTransmitter
LanguageEnglish

Related product manuals