12
2600T SERIES |  PRESSURE TRANSMITTERS |  OI/266/FF-EN REV. E
Pressure Equipment Directive (PED) 
(2014/68/EU)
Devices with PS > 200 bar
Devices with a permissible pressure PS >200 bar have been 
subject to a conformity validation. The data label includes the 
following specifications:
Figure 5: 266 nameplate with PED data 
Devices with PS ≤200 bar
Devices with a permissible pressure PS ≤200 bar correspond to 
article 3 paragraph (3). They have not been subject to a 
conformity validation. These instruments were designed and 
manufactured acc. to SEP Sound Engineering Practices.
Mounting a DP sensor transmitter
The pressure transmitter models 266DSH, 266MST and 266RST 
can be mounted directly on the manifold. A mounting bracket 
for wall or pipe mounting (2” pipe) is also available as an 
accessory. For models 266DRH, 266MRT and 266RRT always 
mounting brackets should be used. Ideally, the pressure 
transmitter should be mounted in a vertical position to prevent 
subsequent zero shifts.
IMPORTANT 
If the transmitter is installed inclined with respect to the 
vertical, the filling liquid exerts hydrostatic pressure on the 
measuring diaphragm, resulting in a zero shift. In such an 
event, the zero point can be corrected via the zero push-
button or via the “set PV to zero” command. Please refer to 
the following paragraph for further details. For transmitters 
without diaphragm seals, please read the considerations on 
the Vent/Drain.
During installation of the transmitter, zero shifts caused by 
mounting (e.g., a slightly oblique mounting position due to a 
remote seal, etc.) may occur; these must be corrected.
IMPORTANT 
The transmitter must have reached its operating 
temperature (approx. 5 min. after startup, if the transmitter 
has already reached the ambient temperature).
This correction can be executed only if the Calibration 
Lower Range value is 0.0 and must be made with process 
(dp or p) = 0.
The correction consists in the Zero elevation/suppression 
operation and can be done in two ways:
1  Locally by acting on the Z push button when the electronic 
switch SW 3 is set to 0,
2  From remote station via FF communication writing 0.0 in the 
PTRB_DESIRED_PRIMARY_VALUE
In case the Calibration Lower Range value is not 0.0 then the 
correction cannot be made with the local Z push button, but it 
can be done only from remote station via FF communication 
writing the correct measure value in the PTRB_DESIRED_
PRIMARY_VALUE
IMPORTANT 
After the above operations the Calibration Range Values are 
not changed. The desired process output value is produced 
through an internal calculation by applying an offset at the 
measured value.
NOTICE  
In case of a High Static differential pressure transmitter 
(266DSH.x.H) please always open the equalization valve of 
the manifold (if installed) before applying pressure to the 
transmitter. High Static pressure can damage the sensor 
causing a zero shift and a serious decrease of the total 
performance in terms of accuracy. In this case, please 
perform a full sensor trim.
It is important to mount the transmitter and to lay the process 
piping so that gas bubbles, when measuring liquids, or 
condensate when measuring gases, will flow back to the 
process and not enter the transmitter measuring chamber.
Optional Vent/drain valves (code V1/V2/V3) on the transmitter 
are located on the sensor flanges.
The transmitter has to be positioned so that these drain/vent 
valves will be located higher than the taps on liquid service in 
order to allow the venting of entrapped gas or below the taps 
on gas service in order to allow the air to vent off or condensate 
to drain off.