2600T SERIES | PRESSURE TRANSMITTERS | OI/266/FF-EN REV. E
Idx Parameter Description / Range / Selections / Note
INTEG_TYPE
Defines the type of counting (up or down) and the type of resetting (demand or periodic)
Not Initialized
UP AUTO
UP DEM
DN AUTO
DN DEM
PERIODIC
DEMAND
PER & DEM
INTEG_OPTS
A bit string to configure the type of input (rate or accum.) used in each input, the flow direction to be considered in the totalization,
the status to be considered in TOTAL and if the totalization residue shall be used in the next batch
(only when INTEG_TYPE = UP_AUTO or DN_AUTO).
Flow Forward
Flow Reverse
Use Uncertain
Use Bad
Carry
Add zero if Bad
Confirm Reset
Generate Reset Event
CLOCK_ERR Establishes the period for periodic reset, in seconds
PRE_TRIP
Value used for the OUT_PTRIP setting. It adjusts the amount of mass, volume or energy that should
set OUT_PTRIP when the integration reaches (TOTAL_SP - PRE_TRIP) when counting UP or PRE_
TRIP when counting DOWN. Expressed in OUT_RANGE Unit
N_RESET
The number of resets is counted in the register N_RESET. This counter can not be written or reset. It provides verification that the
PCT_INCL This value is the % of the absolute net increment with good status respect of the absolute net increment regardless of the status.
GOOD_LIM If PCT_INCL ≥ GOOD_LIM and the mode is AUTO the status of the OUT is GOOD_NC otherwise check the other limit. Expressed in %
UNCERT_LIM If PCT_INCL ≥ UNCERT_LIM and the mode is AUTO the status of the OUT is UNCERTAIN otherwise is BAD. Expressed in %
OP_CMD_INT
OFF
Operator reset command. Resets the totalizer
ON
OUTAGE _ LIM
The max, tolerated duration for power failure. This value is used by the host expressed in seconds
RESET_CONFIRM
OFF
not received in input to the RESET_CONFIRM. If not connected it acts like a momentary dynamic
parameter. This ensures that a host has recorded the snapshot values before the next reset can
occur.
CONFIRM
UPDATE_ EVT This alert is generated by any change to the static data
BLOCK_ALM
The block alarm is used for all configuration, hardware, connection failure or system problems in the block. The cause of the alert is
entered in the subcode field. The first alert to become active will set the Active Status in the status parameter. When the
Unreported status is cleared by the alert reporting task, another block alert may be reported without clearing the Active Status, if
the subcode has changed
...Block Mapping